THVA-63 Single phase adjustable over and under voltage over current with voltage display protector
THVA-63
Single phase
Functions:
1.Over voltage :230-300V
2.Under voltage :140V--210V
3.Over current : 1-63A
Functions:
1.Over voltage :230-300V
2.Under voltage :140V--210V
3.Over current : 1-63A
Delivery
FOB
minimum order
100 pieces
Supply Ability
3000pieces / Month
Country of Origin
China
Stock Time
15Day
Quantity
Over under voltage protector Over under voltage protector
Functions:
1.Over-voltage protection
2.Under-voltage protection
3.Over-current protection
4.Automatic recovery
5.Voltage display(voltage measurement)
6.Current display (current measurement)
7. Voltage calibration: Voltage +-10% adjustable. A13
8. Restore factory settings: press the down button for more than 12s
9.Fault inquiry: Press the UP button from more than 12S
Product Parameters:













1.Over-voltage protection
2.Under-voltage protection
3.Over-current protection
4.Automatic recovery
5.Voltage display(voltage measurement)
6.Current display (current measurement)
7. Voltage calibration: Voltage +-10% adjustable. A13
8. Restore factory settings: press the down button for more than 12s
9.Fault inquiry: Press the UP button from more than 12S
Product Parameters:
| Model number | THVA-63 |
| Power supply | 230VAC 50/60Hz |
| Max.Loading power | 230VAC 50/60Hz |
| Over-voltage protection value range | 230V~300~OFF(default:270V) |
| Over-voltage recovery voltage range | 225V--295V(default:250V) |
| Over-voltage protection action time | 0.1s~30s(default value:0.5s) |
| Over-voltage recovery delay time | 1s~500s(default:30s) |
| Under-voltage protection value range | 140V--210V --OFF(default:170V) |
| Under-voltage recovery voltage range | 145V--215V (default:190V) |
| Under-voltage protection action time | 0.1s~30s(default:0.5s) |
| Under-voltage recovery delay time | 1s~500s(default:30s) |
| Over-current adjustment range | 1-40A (default:20A)1-63A (default:40A) |
| Over-current action range | 0.1~30 second (default:0.5s) |
| Over-currentrecovery delay time | 1s~500s(default:30s) |
| Power-on delay time | 1s~500s(default:10s) |
| Power consumption | <2W |
| Electric machinery life | 100,000 times |
| Installation | 35mm DIN rail |